Chlorination System MR 50 RC

Products

The MR 50 RC Chlorinator System is designed for  dosing larger amounts of gas chlorine (up to 120kg) and with minor alterations, also other gases, working on the indirect vacuum principle.

Add to inquiry list

GENERAL

The MR 50 RC Chlorinator System is designed for   dosing larger amounts of gas chlorine (up to 120kg) and with minor alterations, also other gases, working on the indirect vacuum principle.

The MR 50 RC System consists of:

· M 50 C vacuum regulator

· M 350 C ejector

· M 250 C gas flowmeter

OPERATION PRINCIPLE

Dosing can be set manually with the rate valve of the gas flowmeter. It starts or stops when the ejector pump switches on or off.

SYSTEM EXTENTION OPTIONS

The MR 50 RC System can be additionally equipped with motor valve for automatic dosing of gas. It can easily be switched from automatic to manual operation.

Technical data

Accuracy
Within 4% of the flow
Operating range
20:1
System weight
54kg

Connections

Vacuum (up to 15m)
60kg/h
d50 - 2"
80kg/h
d50 - 2"
120kg/h
d50 - 2"
160kg/h
d50 - 2"
200kg/h
d50 - 2"

Pressure

Flange connection D3/4’’ NP16 DN20  (DIN2633)

from 60  to 120 kg

Ejector connection:

See product info for high capacity ejectors M 350.

Other connections on request!

Documents

BUL00026.pdf
Add to inquiry list

Interested in a custom tailored solution?

Contact us