AKN- Full vacuum Automatic Chlorinator M 3610 C

Products

Capacity up to 15 kg/h

  • 4 –20 mA proportional control input
  • Modbus Communication
  • 5-POINT valve calibration
  • Manual or automatic control
  • Led indication of the valve position
  • Vacuum indication
  • Made of quality materials
  • High quality stepper motor
  • V-notch precision rate valve
Add to inquiry list

General

Automatic chlorinator series M 3610 C is a heavy duty feed unit intended for accurate manual or automatic feed of chlorine gas. The unit is controlled via controller (automatic control) or in case of need it can simply be switched to manual control.

The unit M 3610 C consist of:

  • Motor rate valve series M 3531 C 
  • ERB gas flow meter of corresponding capacity with manual rate valve
  • Vacuum switch (high/low)
  • Vacuum gauge 
  • Wall mounting board with piping 
  • DP regulator

Electromotive rate valve Series M 3531 C is made of compact plastic, resistant to high concentration of chlorine, precision rate valve and quality driving motor. Gas flowmeter is also made of compact plastic and glass, resistant to high concentration of chlorine and precision manual rate valve. All seals are made of materials resistant to aggressive gases (FKM, PTFE, PVDF). Differential pressure regulator is available in case of long vacuum lines or fluctuating vacuum.

General

One must have in mind that M 3610 C is a vacuum device, therefore gases are not pushed, but sucked through. Gas enters in inlet and goes through the gas flow meter. Next, through the needle of rate valve, desired quantity is provided. Then, gas enters the DP REGLATOR, where vacuum fluctuations are reduced. Last element is check valve that disables backflow.

Automatic chlorinator is connected to AQUACON M 5500 C or AQUAProcessor series M 5700 C, which opens or closes the motor valve on chlorinator according to the signal received from water flow meter and/or residual chlorine analyser. In case of controller malfunction, the feed rate can easily be set manually on the motor valve. In case of motor valve failure, manual feed can be adjusted by rate valve on the gas flow meter.

Motor valve can then easily be dismounted from chlorinator. When repaired, it can easily be assembled back and set into operation.

Dosing range

up to 15 kg/h

Gas type

Cl2, SO2

Connections

kg/h
Vacuum line (max. 15m)
2
d8/d10 - 3/8''
4
d8/d10 - 3/8''
10
d12/d16 - 5/8''
15
d12/d16 - 5/8''

For larger vacuum lines, see table: Chlorine vacuum line size requirements

Electrical data

Power supply
24 V + 20 / -30%
Valve power supply
24 VDC nominal, 20 - 30 VDC
Consumption
30 mA
Current limitation at the output Q1 and Q2
220m

Sensor

Area
MIN -100000 Pa (-100 kPa, -1 bar)
MAX 0 Pa
Accuracy
1%

Alarm

Operating mode
active HIGH, active LOW
Reference
area
Hysteresis
1% .. 10% of the area

Digital output Q

Operating mode
  • Off
  • When the alarm activated 24 VDC, otherwise off
  • When 0 VDC alarm turns on, otherwise off
  • When the alarm activated 24 VDC, otherwise activated 0 VDC

Mechanical data

Protection
IP 67
Accessories
PVC-U 16 (PN16)

Data for rate valve: see product M 3531 C 

Documents

BUL00065_AKN_Full_vacuum_automatic_chlorinator_M_3610_C.pdf
Chlorine_vacuum_line_size_requirements.pdf
Add to inquiry list

Interested in a custom tailored solution?

Contact us
Close