Chlorination System MR 20 RC

Products

The M 20 RC Chlorinator System is designed for dosing gas chlorine and with minor alterations other gases, working on the indirect vacuum principle.

Add to inquiry list

Capacity up to 15kg/h

Vacuum principle

GENERAL

The MR 20 RC Chlorinator System is designed for dosing gas chlorine and with minor alterations, also for other gases, working on the indirect vacuum principle.

The MR 20 RC System consists of:

· M 20 C vacuum regulator

· M 300 C ejector

· M 200 C gas flowmeter

Dosing can be set manually on the rate valve of the regulator. It starts or stops when the ejector pump switches on or off.

INSTALLATION

It is very simple to mount vacuum regulators. However, installation of the devices must be done by qualified experts, taking in consideration all required international standards, in order to ensure safe and faultless operation.

An authorized service must overhaul the system once a year.

SYSTEM EXTENSION OPTIONS

Multipoint chlorination system

The MR 20 RC System can be extended by additional gas flowmeters, which have to be installed parallel to the existing one. This way the system can be extended to several dosing points, but in this case, suitable ejector must be added to it. When adding gas flowmeters to the system, it is important not to exceed the capacity of the regulator.

Semiautomatic dosing system

Where there are several pumps in the water-supply system with known capacities, each pump can be extended by ejector and gas flowmeter, and connected parallel to the regulator. Dosing can be blocked through electromagnetic valve. Activation of the electromagnetic valve depends on the known flow changes.

Options

Alarm
yes "A", without alarm the letter is not written in the code
Regulator
"R", means system with all general parts
Gas Type
“C” - Cl2, “CO2” - CO2, “S” - SO2, “N” - NH3
Ejector
"B" - DPT: ejector with PVC valves designed for pool engieneering (pressure up to 6bar)
"T" - reinforced ejector: is used with pressure higher than 6 bar
"P" - Ejector with connection cock: for dismantling under pressure (up to 3 bar, max 4 kg/h)
Pressure Gauge
yes "M", without it the letter is not written in the code
Yoke
for clamp type yoke, the letter "F" is written in the code

Dosing range (g/h)

1
up to 12
2
up to 25
3
up to 100
4
up to 200
5
up to 500
6
up to 1000
7
up to 2000
8
up to 4000
9
up to 10000
15
up to 15000

Technical data

Accuracy
Withing 4% of the flow
Operating range
20:1
Weight
Nett: 5,0kg, Gross: 8,9kg
Packaging Dimensions
600 x 400 x 400mm

Connections

Vacuum (up to 15m)
2kg/h
d8/d10 - 3/8"
4kg/h
d8/d10 - 3/8"
10kg/h
d12/d16 - 5/8"
15kg/h
d12/d16 - 5/8"

For larger vacuum lines, see table: Chlorine vacuum line size requirements.

Connection to the cylinder:

Standard: 1” (complies with DIN  477)

Optionally:

1.030” (CGA)

5/8”  (BSP)

M27x1,5mm

Ejector connection:

See product info for ejectors M 300.

Documents