Automatic Chlorinator M 3603 C

Products

Automatic chlorinator series M 3603 C is a heavy duty feed unit intended for accurate manual or automatic feed of chlorine gas into water. It is designed to be controlled through 4-20mA current signal or ModBUS communication. In case of need, it can simply be switched to manual control.

Add to inquiry list

KEY FEATURES

  • 4 –20 mA proportional control input
  • Modbus Communication
  • 5-POINT valve calibration
  • Manual or automatic control
  • Led indication of the valve position
  • Vacuum indication
  • Made of quality materials
  • High quality stepper motor
  • V-notch precision rate valve
  • Simple installation set up and start up

GENERAL

Automatic chlorinator series M 3603 C is a heavy duty feed unit intended for accurate manual or automatic feed of chlorine gas into water. It is designed to be controlled through 4-20mA current signal or ModBUS communication. In case of need, it can simply be switched to manual control.

The unit M 3603 C consist of:

· Motor rate valve series M 3531 C

· Gas flow meter of corresponding capacity

· Vacuum gauge

· Wall mounting board

Electromotive rate valve Series M 3531 C is made of compact plastic, resistant to high concentration of chlorine gas, precision rate valve and quality driving stepper motor. Gas flow meter is also made of compact plastic, resistant to high concentration of chlorine. All seals are made of fluorocarboned hydrogen’s (FPM/FKM) resistant to aggressive gases. All this   guarantees a safe, long and accurate functioning of automatic chlorinator.

OPERATION PRINCIPLE

Automatic chlorinator is mounted between ejector and vacuum regulator. It is connected to either AQUACON M 5500 C, AQUAProcessor series M 5700 C or directly to SCADA software, through PLC units, which opens or closes the motor valve through 4-20mA current signal or ModBUS communication, according to the signal received from   water flow meter and/or residual chlorine analyser. In case of controller malfunction, the feed rate can easily be set manually on the motor valve (switch remote/manual and switch open/close). In case of motor valve failure, manual feed can be adjusted by manual knob on the top of the motor valve.

Technical data

Weight
6,5kg
Dimension
500 x 300 x 180mm

Connections

Vacuum (up to 15m)
2kg/h
d8/10 - 3/8"
4kg/h
d8/d10 - 3/8"
10kg/h
d12/d16 - 5/8"

For larger vacuum lines, see table: Chlorine vacuum line size requirements

Electrical data

Analog input
Current input
0 .. 4 - 20mA (Internal resistance 100 Ω)
Voltage input
0 .. 2 – 10 V (internal resistance 100 KΩ )
Function
Valve position = Analog input value

Electrical data

Digital input
Electrical function
Internal supply digital input
Maximum voltage
24 V
Maximum current
1 mA
Signal "1"
at 10 V
Signal "0"
at 4V
Function:
Contact normally closed = Valve in operation
Contact open = Valve failure

Electrical data

analog output
Voltage
22 VDC
Current output
4 - 20mA
Function:
Analog output value = Valve position
Analog output value 21,6 mA indicating valve failure. 

Electrical data

Digital output
Electrical function:
Potential-free contact
Maximum voltage:
30 VDC or 24 VAC +10%
Maximum current:
200 mA
Function:
Valve failure (contact is open or closed)

Valve power supply

24 VDC nominal, 20 – 30 VDC

Maximum consumption:  6 W

Documents

BUL00064.pdf
Chlorine-vacuum-line-size-requirements.pdf
Add to inquiry list

Interested in a custom tailored solution?

Contact us
Close