Chlorination System MR 21 RC

Products

The MR 21 RC Chlorinator System is designed for dosing gas chlorine and with minor alterations, also other gases, working on the indirect vacuum principle.

Add to inquiry list

Capacity up to 15kg/h

Vacuum principle

GENERAL

The MR 21 RC Chlorinator System is designed for dosing gas chlorine and with minor alterations, also other gases, working on the indirect vacuum principle.

The MR 21 RC System consists of:

· Two M 20 C vacuum regulators

· M 400 automatic vacuum switch-over

· M 300 C ejector

· M 200 C gas flowmeter

Dosing can be set manually with the rate valve of the regulator. It starts or stops when the ejector pump switches on or off.

OPERATION PRINCIPLE

The MR 21 RC system ensures uninterrupted dosing even when the cylinder is empty or there are several cylinders connected to the collector line. When the cylinders are empty, the Vacuum switchover automatically switches over the vacuum to the       regulator that has full cylinders. This way the system functions without interruption. The empty cylinders can be replaced without having to stop the system of water disinfection.

INSTALLATION

It is very simple to mount vacuum regulators. However, installation of the devices must be done by qualified experts, taking in consideration all required international standards, in order to ensure safe and faultless operation.

An authorized service must overhaul the system once a year.

SYSTEM EXTENTION OPTIONS

The MR 21 RC system can be extended by additional gas flowmeters which have to be installed parallel to the existing one. This way the system can be extended to several dosing points, but in this case, a suitable ejector must be added to it. When adding gas flowmeters to the system, it is important not to exceed the capacity of the regulator.

Options

Alarm
yes "A", without alarm the letter is not written in the code
Regulator
"R", means system with all general parts
Gas Type
“C” - Cl2, “CO2” - CO2, “S” - SO2, “N” - NH3
Ejector
"B" - DPT: ejector with PVC valves designed for pool engieneering (pressure up to 6bar)
"T" - reinforced ejector: is used with pressure higher than 6 bar
"P" - Ejector with connection cock: for dismantling under pressure (up to 3 bar, max 4 kg/h)
Pressure Gauge
yes "M", without it the letter is not written in the code
Yoke
for clamp type yoke, the letter "F" is written in the code

Dosing range (g/h)

1
up to 12
2
up to 25
3
up to 100
4
up to 200
5
up to 500
6
up to 1000
7
up to 2000
8
up to 4000
9
up to 10000
15
up to 15000

Technical data

Accuracy
Withing 4% of the flow
Operating range
20:1
Weight
Nett: 5,0kg, Gross: 8,9kg
Packaging Dimensions
600 x 400 x 400mm

Connections

Vacuum (up to 15m)
2kg/h
d8/d10 - 3/8"
4kg/h
d8/d10 - 3/8"
10kg/h
d12/d16 - 5/8"
15kg/h
d12/d16 - 5/8"

For larger vacuum lines, see table: Chlorine vacuum line size requirements.

Connection to the cylinder:

Standard: 1” (complies with DIN  477)

Optionally:

1.030” (CGA)

5/8” (BSP)

M27x1,5 mm

Ejector connection:

See product info for ejectors M 300.

Documents

BUL00024.pdf
Chlorine-vacuum-line-size-requirements.pdf
Add to inquiry list

Interested in a custom tailored solution?

Contact us